National Electrical Code Top Ten Tips:
Article 225, Outside Branch
Circuits and Feeders
Please note, we do quote from copyrighted material. While the NFPA
does allow such quotes, it does so only for the purposes of education
regarding the National Electrical Code. This article is not a substitute
for the NEC.
These are the 10 NEC Article 225 items we deem most important, based
on the pervasiveness of confusion and the potential costs of same.
- NEC 225.1. Read the scope carefully. In many instances of
disagreement with the electrical inspector, folks are misapplying
NEC 225.
- NEC Table 225.2 clearly shows were other NEC Articles apply to
specific equipment and conductors.
- NEC 225.4. Overhead conductors outdoors must be insulated or covered (per
Article 100, a covering is not insulation) when within 10 feet of a
building—except as stated.
- NEC 225.7 gives various rules for outdoor lighting. Note, there
are clearances established for circuits exceeding 120V.
- NEC 225.14 provides the rules for open conductor spacing. For
example, "Open conductors shall be separated from open
conductors of other circuits or systems by not less than 100 mm (4
in.).
- NEC 225.18 is "Clearance from Ground." This has often
been a source of contention in court. It’s best to exceed the
requirement by a foot or two, as design and installation are two
different things and being off by an inch can burn you, despite the
fact that it’s substantial compliance and obviously satisfies the
intent of the Code. For one thing, a crane operator won’t know you
are an inch low, and that can get somebody killed. These are minimal
heights. Pay attention to the type of area a cable will pass over,
and use the highest clearance if in doubt. Also, create a clear path
for fire ladder equipment and other emergency apparatus.
- NEC 225.19 gives the clearances from buildings—the comments we
gave for NEC 225.18 also apply here.
- NEC 225.34 addresses the grouping of disconnects. You can have a
single disconnect on a service. But, if you have more than one, you
must group all of them (except a fire pump disconnect, which has
special requirements) . You can have a maximum of 6 disconnects per
service entrance.
- NEC 225.37 covers an issue most installers routinely ignore or
inadequately comply with. You must have a circuit directory or
plaque (with some exceptions noted) to identify the circuits. The
intent here is not to have vague text, but to clearly identify the
circuits. This isn’t just for the convenience of the owner. It’s
also for the use of the first responders (e.g., for stopping an
electrocution), fire department workers and other emergency workers.
It is illegal to shirk responsibility here, and this particular
violation can carry heavy personal penalties for all concerned.
- NEC 225.60 and NEC 225.61 provide more information on clearances,
such as those over sidewalks.
Learn more about Article 225 with the Mike
Holt NEC General Requirements course:
http://www.mindconnection.com/Merchant2/merchant.mvc?
Screen=PROD&Product_Code=TRN-HLT-NEC-090-240&
Category_Code=TRN-ELECT-NEC
|