construction code books

Home | Search | About us                  Bookmark and Share

 
nec training

National Electrical Code Articles and Information

Based on the 2011 NEC

by Mark Lamendola

National Electrical Code Top Ten Tips: Article 590, Temporary Installations

  1. Article 590 covers the installation of temporary power and lighting [590.1].
     
  2. Contrary to common misconception, temporary installation requirements are "shortcut tolerant." That isn't their purpose. In fact, all other Articles apply to these installations [590.2(A)] except for modifications provided in this Article. The purpose of this Article is to allow for the fact such installations will be removed within a short time of being installed.
     
  3. Temporary installations are acceptable only if approved based on the conditions of use and any special requirements of the temporary installation [590.2(B)].
     
  4. Temporary installations are, by definition, time-constrained. The NEC defines three periods: during construction, 90 days, and emergencies/tests [590.3].
     
  5. At the end of the period for which the installation was implemented, it must be removed [590.3].
     
  6. There are no special allowances for services. These must be installed as if they are permanent [590.4].
     
  7. For feeders and branch circuits, the basic exception for temporary installations is you can wire the circuits using Type NM and Type NMC cables [590.4]. Every other requirement still applies, and in some cases with even more stringency than for permanent installations; for example, all receptacles must be of the grounding type.
     
  8. Luminaires for temporary circuits have special requirements. For example, they must all have protection against accidental contact or breakage [590.4)F)].
     
  9. All wiring must be ground fault protected [590.6]. The exception to this is where you have an assured grounding program. Such a program is so difficult to maintain and properly document that generally this exception is not an option.
     
  10. But some companies are successful with their assured grounding program. If you want to consider this, the requirements are in 590.6.

Don't take your electrical exam twice

Journeyman Electrical Exam Prep | Master Electrician Exam Prep

Learn more about: Harmonics | Motors | Power Quality
 

How the NEC is arranged

  1. The first four Chapters of the NEC apply to all installations.
  2. Article 90 precedes Chapter One, and establishes the authority of the NEC.
  3. Article 80 follows the body of the NEC; it exists as Annex H. It provides the requirements for administration.
  4. Chapters 5, 6, and 7 are the "special" chapters, covering special: occupancies, equipment, and conditions (in that order).
  5. Chapter 8 provides the requirements for communications systems.
  6. Chapter 9 provides tables.
  7. The appendices provide mostly reference information.
  8. Appendix D contains examples that every NEC user should study.

Try your NEC moxy:

  • Do you know the difference between bonding and grounding? Hint: Look in the NEC, Article 100.
  • Does the NEC refer to grounding incorrectly in any of its articles? Yes! So be careful to apply the Article 100 definitions. Don't ground where you should bond.
  • When doing motor load calculations, which Article covers hermetic motors? Answer: While Article 440 covers the application of hermetic motors, it does so only by amending Article 430 because hermetic motors are a special case of motors. For motor load calculations, refer to Article 430.
  • Does the NEC provide a voltage drop requirement? Yes! It does so in a special case, which is Article 648 Sensitive Electronic Equipment. But for general applications, it does not provide a requirement; it merely provides a recommendation in a couple of FPNs.
  • Take our Code Quizzes.

Remember other applicable codes, rules, standards, and references:

  • OSHA's electrical worker safety rules.
  • IEEE standards.
  • NETA standards.
  • NFPA standards.
  • International Codes (if applicable to the installation).
  • State Codes (if the state has them).
  • Local ordinances and permit requirements.
  • Local fire codes.
  • Manufacturer requirements or guidelines.
  • Customer security requirements.
  • Industry standards.
  • Your company's own internal standards, practices, and procedures.
  • Engineering drawing notes.

 

 

 

Master the NEC | Solve Harmonics | Become a Motor Maintenance Guru

Codebookcity is a subsidiary of Mindconnection, LLC. If you have any questions, comments, or concerns, please write to sales @ mindconnection.com. We do want your business.