[300.9]. A wet location. The conductors, thus, must comply with
310.10(C).
[300.10]. Join them into a continuous electrical conductor. With
nonmetallic, you can't do this--and thus other bonding requirements
apply. They also, regardless of composition, must be mechanically
continuous [300.12].
[300.11]. Trick question. This is prohibited.
[300.11]. Yes. There are different rules for fire-rated and nonfire-rated.
[300.11]. No. You can't hang anything from raceway. Raceway is not a
support for other wiring. Nor can you use cable or wiring to support
raceway.
|